Paris Data Centre

Appointed to analyse a protection issue at a Data Centre in Paris. The standby generators were tripping on differential protection.

Hyperscale Project

Project overview

The Issue – Appointed to analyse a protection issue at a Data Centre in Paris. The standby generators were tripping on differential protection.

Lagan Energy Location Pin

Location

Paris

Lagan Energy Icon

Duration

4 Weeks

Lagan Energy Icon

Voltage Level

20kV

Paris Data Centre
Hyperscale Project

Review

We discovered the differential relay was programmed as a generator-only, whereas the correct program should have been a generator-transformer differential relay, due to the zone of protection coverage determined by the position of the CT’s installed either side of the HV/LV transformer.

Primary injection testing revealed that the orientation of the generator LV CT’s were in reverse polarity, resulting in the differential scheme identifying an in-zone fault for ‘through-load’ generator operations.

Paris Data Centre
Hyperscale Project

Our Solution

We proposed alternative settings and logic for the generator differential relays (8x in total) to account for the HV/LV transformer being within the differential zone.

The client accepted our proposal in which we fully implemented into the relays and commissioned; generator LV CT polarity reversed by our Commissioning Team.

Generator load checks performed with differential schemes ‘stable’ after all changes made.